Nominal voltage 120/240 V 60 Hz, single phase
-
Listed to UL1008 Transfer Switch Equipment and CSA Certified to CSA 22.2 No. 178-1978
Automatic Transfer Switches
-
Meets National Electrical Code (NEC) and National Fire Protection Association (NFPA)
requirements.
-
True double-throw contacts (no intentional off position), with inherent mechanical
interlocking to prevent connection of generator and utility source.
-
Convenient terminals to connect neutral and ground conductors from service and load feeders.
|
-
3-second time delay to override momentary utility source
-
15-second transfer to emergency time delay to allow engine generator to stabilize after
starting
-
15-second time delay after transfer to the standby source to ignore momentary voltage dips
on the generator during initial loading
-
5-minute time delay on retransfer to allow utility source to stabilize prior to transferring
the load back to utility
-
1-minute unloading running time delay for engine generator cool-down before shutdown
|